6 MONTHLY FILTER AND LAMP INSPECTION ON CCR CONTROL DISPLAY UNIT (DCS-OVERVIEW)
6 MONTHLY
FILTER AND LAMP INSPECTION ON CCR CONTROL
DISPLAY UNIT
(DCS-OVERVIEW)
Control Room Overview Screen
Lamp Change out.
TASKS TO BE
PERFORMED:
WARNING: THE LAMP MODULE MUST BE
SWITHED OFF FIRST, THEN ALLOWED TO COOL DOWN FOR 5 MINUTES BEFORE THE POWER IS
SWITCHED OFF.
1. Remove back panels of the CCR
overview screen.
2. Switch off all the lamps by
pressing STOP on each module.
3. WAIT 5 MINTUES.
4. Switch off power on each
module by pressing OFF.
5. Remove filter pad from each
module.
6. Remove to workshop and clean
filter pad using airline, if the filter is excessively blocked, replace with
new filter.
7. Install filter pads in the
correct direction as indicated on the side of the filter.
8. Switch on power by pressing
ON, at each module.
9. Switch on lamp by pressing
START at each module.
10. Sign-off Work Permit and return
to operations.
11. Report all findings to
supervision and document in CMMS.
CHECK WITH CONTROL ROOM AND
CAUSE AND EFFECTS AND PLACE OVERRIDE ON AUGUST SAFETY SYSTEM.
ANY REQUIRED OVERRIDE MUST BE IN
PLACE PRIOR TO COMMENCING WORK.
ENSURE OVERRIDE IS PLACED IN THE
OUT OF SERVICE POSITION.
1 MONTHLY PREVENTIVE MAINTENANCE
ON ALL INSTRUMENTATION ON WEST HP FLARE IGNITION SYSTEM
TASK TO BE
PERFORMED:
INSPECTION AND FUNCTION TESTING
OF FLARE SYSTEMS CONTROL PANEL AND ALL INSTRUMENTS.
CHECK PANEL MOUNTED INSTRUMENT
AIR, PILOT GAS AND IGNTION GAS PRESSURE GAUGES RANGE 0-30 PSIG.
1. Annual Inspection and
Calibration of Pressure Gauges.
2. Inspect Pressure Gauge for
any physical damage.
3. Check Pressure Gauge is
securely mounted.
4. Check Pressure Gauge for
vibration.
5. Ensure gauge glass is secured
correctly and is not cracked or broken.
6. Check Pressure gauge pointer
for any pulsation and is not bent
7. Isolate and vent pressure
gauge.
CHECK PANEL MOUNTED INSTRUMENT
AIR, PILOT GAS AND IGNITION GAS PRESSURE REGULATORS
8. Inspection and testing of
Pressure Regulator.
9. Inspect Pressure Regulator
for any physical damage.
10. Ensure Pressure Regulator is
securely mounted.
11. Check all connections and
fittings are secure and check there are no leaks.
12. Check Valve body flange
bolts are tight and there are no leaks.
13. Check Valve stem packing for
leaks and carefully tighten if required. Do not over-tighten.
14. Check Valve Actuator Bonnet
bolts are tight and there are no leaks.
15. Check supply line fittings
are tight and no leaks exist. Do not over-tighten.
16. Increase and decrease the
regulator setting and ensure the output pressure responds correctly.
17. Adjust the pressure
set-point of the Air and Ignition Gas to 1.04 BARG.
18. Adjust the pressure
set-point of the Pilot Gas to 0.69 BARG
19. with the enclosure Power
OFF, and purge system air supply on:
20. Test operation of the
enclosure vent and seal the enclosure.
21. Adjust the enclosure flow
meter until the value reads 60 SCFH.
22. Purge the enclosure for a
Minimum of 3 minutes at the above flow rate.
23. Upon completion of the purge
time, adjust the flow control to a rate that maintains a minimum of 4mm H2O
pressure on the Magnehelic pressure gauge.
24. Ensure this pressure is
4mmH2O and only then energize the power to the ignition panel.
25. Upon successful testing of
the ignition circuit of the flare pilot, de-energize the power to the panel
before removing the positive pressure to the enclosure.
26. If several tests of the
ignition circuit are made are made, ensure the positive pressure is always
maintained to the enclosure.
IF AT ANY TIME POSITIVE PRESSURE
IS LOST TO THE ENCLOSURE, DE-ENERGISE POWER IMMEDIATELY AND START THE PROCEDURE
FROM STEP NO. I. (REPEAT THE PURGE SEQUENCE AGAIN AND RE-ESTABLISH A POSITIVE
PRESSURE AGAIN BEFORE RE ENERGIZING THE PANEL ENCLOSURE.
27. Turn power on to the
Ignition Panel. The three "pilot failure" lights will illuminate if
the flare is not lit. If the flare is lit the three "pilot failure"
lights will not illuminate.
28. Depress the Ignition button
while checking for a spark in the sight glass. Release the Ignition button when
a spark is confirmed. Close all three G4 valves.
29. Open the Pilot gas valves G1
and G5 to establish pilot gas flow to the flare tip.
30. Ensure Pilot gas pressure
should is set at 0.7 - 1.04 BARG refer to panel gauge.
31. Open air valve A2, ignition
gas valves G2 and G3, and only one G4 valve and establish ignition gas flow to
the pilot tip.
32. Ignition air and gas
pressure should be set at 1.04 BARG. Purge the ignition line to the pilot tip
for approximately 20 seconds.
33. Press and release the
Ignition button while checking for a steady flame in the sight glass and
ignition at the pilot tip.
34. When a flame is confirmed in
the sight glass, close the ignition gas valves G3 and G4. When the temperature
elements at the pilot tip are lit, the "pilot failure" light will go
out. IF THE FLARE IS LIT THE PILOT FAILURE LIGHTS WILL NOT BE ILLUMINATED.
35. Open Panel and inspect unit
for any damage or loose connections, tighten connections as required.
36. Clean interior of panel
carefully and remove all dust and sand.
TEMPERATURE SWITCH UNITS
37. Inspect temperature switch
units for any physical damage.
38. Ensure units are securely
mounted.
39. Ensure all alarms are now
reset.
40. ENSURE OVERRIDE IS REMOVED
AND THE SYSTEM IS RETURNED TO NORMAL MODE
41. Turn power off to the
Ignition Panel.
42. Sign-off Work Permit and
return to operations.
43. Report all findings to
supervision and document in CMMS.
Commentaires
Enregistrer un commentaire