Preventive Maitenance: Testing of UV/IR Flame Detectors Injection Compressor

INJECTION COMPRESOR   FLAME DETECTORS(UV/IR): REFER TO CAUSE AND EFFECT DIAGRAMS AND SELECT THE CORRECT KEY SWITCH TO BE PLACED IN THE BY-PASS MODE ON THE CONTROL PANEL AREA MATRIX ON THE FIRE & GAS PANEL PRIOR TO COMMENCING TEST PLACE THE SELECTED SWITCH IN THE BY-PASS MODE ON THE CONTROL PANEL AREA MATRIX ON THE FIRE & GAS PANEL AND CONFIRM THE CORRECT BY-PASS LIGHT IS ILLUMINATED ENSURE THE CORRECT AREA IS BY-PASSED PRIOR TO COMMENCING TEST ENSURE AKUSTA PANEL IS TURNED TO MANUAL PRIOR TO COMMENCING TEST NOTE: WRITE THE MODEL AND SERIAL NUMBER OF THE EQUIPMENT ON THE WORK ORDER. NOTE: Two Technicians required to perform this task The technicians will be in radio contact at all times One technician to be stationed at the Fire and Gas Detection Panel in the Main Control Room. TASK TO BE PERFORMED Testing of UV/IR Flame Detectors NOTES: 1.CLEAN ALL INSTRUMENTS AS REQUIRED 2.RAISE A CORRECTIVE WORK ORDER TO REPAIR ANY FAULTS FOUND TA...